Electric Power Copper Cable with PVC Sheathed
-
Price:
Negotiable
- minimum:
- Total supply:
-
Delivery term:
The date of payment from buyers deliver within days
-
seat:
Jiangsu
-
Validity to:
Long-term effective
-
Last update:
2017-11-08 02:12
-
Browse the number:
209
+
Yangzhou Shuguang Cable Co., Ltd.
- Contactaixin:
Ms. Betty Cao(Mr.)
- Email: telephone: phone:
-
Arrea:
Jiangsu
Address:12th Floor, Integrity Tower, No.547 Museum Road, Hanjiang District, Yangzhou, Jiangsu, China 225652
- Website:
+
Electric Power Cable With PVC Sheath
Standard implemented
The product conforms to the GB/T 12706,IEC 60502,IEC 60840 and IEC 62067. Its flame retardant property has reached the corresponding requirement in GB/T18380.3-2001; Burning smoke intensity (luminousness) is up to the low-smoke standard of GB/T17651-1998; Burning gas lorrosion intensity is in conform to the standard requirement in GB/T17650-1990; The luminousness of burning low halogen and low smoke cable and the liberation of HCl active gas is conform to the standard requirement of Q/321084KLA 051-2004.
Service characteristic
For normal use of halogen free low smoke cable, the permitted longtime operating temp. Of conductor is 90 deg. C; For short circuit (the longest time is 5 seconds), the max temp. Of conductor should not exceed 250 deg. C. For low halogen low smoke cable, the permitted longtime operating temp. Of conductor should not exceed 70 deg. C; For short circuit (the longest time is 5 seconds), the max temp. Of conductor should not exceed 160 deg. C.
The lowing temp. For laying cables is 0 deg. C. As for shortest bend radius: For cables without sheath, it should not be shorter than 10 times of outer diam; For cables with sheath; It should not be shorter than 15 times of outer diam.
Standard implemented
The product conforms to the GB/T 12706,IEC 60502,IEC 60840 and IEC 62067. Its flame retardant property has reached the corresponding requirement in GB/T18380.3-2001; Burning smoke intensity (luminousness) is up to the low-smoke standard of GB/T17651-1998; Burning gas lorrosion intensity is in conform to the standard requirement in GB/T17650-1990; The luminousness of burning low halogen and low smoke cable and the liberation of HCl active gas is conform to the standard requirement of Q/321084KLA 051-2004.
Service characteristic
For normal use of halogen free low smoke cable, the permitted longtime operating temp. Of conductor is 90 deg. C; For short circuit (the longest time is 5 seconds), the max temp. Of conductor should not exceed 250 deg. C. For low halogen low smoke cable, the permitted longtime operating temp. Of conductor should not exceed 70 deg. C; For short circuit (the longest time is 5 seconds), the max temp. Of conductor should not exceed 160 deg. C.
The lowing temp. For laying cables is 0 deg. C. As for shortest bend radius: For cables without sheath, it should not be shorter than 10 times of outer diam; For cables with sheath; It should not be shorter than 15 times of outer diam.
Specification | |||||||
Types | Core No. | Rated Vpltage(kV) | |||||
Cu Core | Al Core | 1.8/3 | 3.6/6 6/6 | 6/10 8.7/10 | 8.7/15 12/20 | 18/20 26/35 | |
Cross Section (mm2) | |||||||
YJV YJY YJV32 YJV33 YJV42 YJV43 | YJLV YJLY YJLV32 YJLV33 YJLV42 YJLV43 | 1 | 10~800 10~1000 10~1000 10~1000 10~1000 10~1000 | 25~1200 25~1200 25~1200 25~1200 25~1200 25~1200 | 25~1200 25~1200 25~1200 25~1200 25~1200 25~1200 | 35~1200 35~1200 35~1200 35~1200 35~1200 35~1200 | 50~1200 50~1200 50~1200 50~1200 50~1200 50~1200 |
YJV YJY YJV22 YJV23 YJV32 YJV33 YJV42 YJV43 | YJLV YJLY YJLV22 YJLV23 YJLV32 YJLV33 YJLV42 YJLV43 | 3 | 10~300 10~300 10~300 10~300 10~300 10~300 10~300 10~300 | 25~300 25~300 25~300 25~300 25~300 25~300 25~300 25~300 | 25~300 25~300 25~300 25~300 25~300 25~300 25~300 25~300 | 35~300 35~300 35~300 35~300 35~300 35~300 35~300 35~300 | 35~300 35~300 35~300 35~300 35~300 35~300 35~300 35~300 |
Nominal Cross Sectional (mm2) | The Largest D.C. Resistance of Conductor at 20ºCΩ/km | Nominal Cross Sectional (mm2) | The Largest D.C. Resistance of Conductor at 20ºCΩ/km | Nominal Cross Sectional (mm2) | The Largest D.C. Resistance of Conductor at 20ºCΩ/km | |||
Cu Core | Al Core | Cu Core | Al Core | Cu Core | Al Core | |||
1.5 | 12.1 | - | 35 | 0.521 | 0.868 | 240 | 0.0754 | 0.125 |
2.5 | 7.41 | 12.1 | 50 | 0.387 | 0.641 | 300 | 0.0601 | 0.1 |
4 | 4.61 | 7.41 | 70 | 0.268 | 0.443 | 400 | 0.047 | 0.0778 |
6 | 3.06 | 4.61 | 95 | 0.193 | 0.32 | 500 | 0.0366 | 0.0605 |
10 | 1.83 | 3.08 | 120 | 0.153 | 0.253 | 630 | 0.0283 | 0.0469 |
16 | 1.15 | 1.91 | 150 | 0.124 | 0.206 | 800 | 0.0211 | 0.0367 |
25 | 0.727 | 1.2 | 185 | 0.0991 | 0.164 | 1000 | - | 0.0291 |
Serial No. | Item of Property | Rated Voltage U0/U kV | |||||||
1.83/3 | 3.6/6 | 6/6 6/10 | 8.7/10 8.7/15 | 12/20 | 18/20 18/30 | 21/35 | 26/35 | ||
1 | Partial discharge test 1.73U0 should not be greater than | / | 10 | 5 | |||||
2 | Industrial frequency 5 min voltage endurance test(kV) | 6.5 | 12.5 | 21 | 30.5 | 42 | 63 | 73.5 | 91 |
3 | 4h industrial frequency test(kV) | 7.2 | 14.4 | 24 | 34.8 | 48 | 72 | 84 | 104 |
4 | Heat extension test(200ºC 15 min 20N/cm) under pressure load extension rate max% Permanent extension rate max after cooling% | 175/15 | |||||||
5 | Partial discharge 1.5U0 after three times of curing and heat cycling should not be large than(pC) | 20 | 5 | ||||||
7 | Flame-retarding property test | Conforms to the standard of IEC60 332-2C |